ECTOR
Type: TCI2-222.200
24V AC/DC
N
L
L
GND V+
DO1 DO1 DO2 DO2
24V AC/DC
3 VA
Power
Digital Output (2x)
Status LED
UI1/2
NTC Input (2x)
NTC 10k 
GND UI1 UI2
UI3
GND UI
GND
UI
NTC
10k 
Configuration of in- and outputs
The inputs and outputs are configured with jumpers. Jumpers are located underneath the controller.
AO: Selection of analog output type
Left position:
voltage output (0... 10 V)
factory default
Right position:
current output (0... 20 mA)
See the TCI2 installation sheet, document no. 70-00-0688 or 70-00-0893 (www.vectorcontrols.com).
Status-LED
The TCI2 has a status-LED which is located on the upper left side of the controller housing.
The location of the LED is described in the installation sheet. The function of the LED is explained in the X2 Operations Manual.
Rest button TCP/IP (-WEM, -WEB, -ETM, -ETB only)
The TCP/IP configuration setting of the TCI2 can be reset by pressing the reset button with a 1 mm pin through the small hole
located next to the Status-LED. The function of the TCP/IP reset is explained in the X2 Wi-Fi / Ethernet Configuration Manual.
Doc: 70-07-0703B, 20220426
Subjects to alteration
N
N
Relays 3A
UI3/4
VDC Input (2x)
0...10 VDC
GND
UI4
GND
UI
0...10 VDC
OPT1-xx
OPA2-xx
AO1
© Vector Controls LLC, USA
_
+
REF
Operation
Terminal
JP7
120 Ω
OP1
OP2
OP3
OP4
_
+
Vop
STP
1
2 3
4
OPXX-VC
UI: Selection of universal input type
Left position:
voltage output (0... 10 V)
factory default
Middle position: current input (0... 20 mA)
Right position: RT or dry contact
www.vectorcontrols.com
TCI2
P
D
S
RODUCT
ATA
HEET
UI1
Page 6-10