Vector TCI2 Product Data Sheet page 9

Universal programmable controller
Hide thumbs Also See for TCI2:

Advertisement

V
ECTOR
Supported BACnet Interoperability Blocks (BIBB)
The BACnet interface conforms to the B-ASC device profile (BACnet Application Specific Controller).
The following BACnet Interoperability Building Blocks (BIBB) is supported.
BIBB
DS-RP-B
DS-RPM-B
DS-WP-B
DS-COV-B
DM-DCC-B
DM-DDB-B
DM-DOB-B
DM-TS-B
DM-UTC-B
DM-RD-B
Supported standard BACnet application services
- ReadProperty
- ReadPropertyMultiple
- WriteProperty
- ChangeOfValue
- DeviceCommunication (password protected)
- I-Am
- I-Have
- TimeSynchronisation
- UTCTimeSynchronisation
- ReinitializeDevice ("cold" or "warm") (password protected)
Supported standard Object types
- Device
- Analog input
- Analog value
- Binary value
- Multi-state Value
- Network Port
X2 Functional Scope
The controller has the following X2 functions and elements:
Group
Modules
UP
01U to 04U
UI
05U to 08U
AL
1AL to 8AL
LP
1L to 2L
AO
1A to 2A
FAN
1F
DO
1d to 2d
1FU
2FU
FU
3FU
4FU
5FU
CO
-
COPY
-
RTC
-
PRO
Pr01 to Pr12
Doc: 70-07-0703B, 20220426
Subjects to alteration
Type
Data sharing
Data sharing
Data sharing
Data sharing
Device management
Device management
Device management
Device management
Device management
Device management
QTY
Description
User and display parameters
4
Universal inputs, selectable with jumper: RT/DI, mA, VDC
4
Virtual inputs for operation terminals, bus modules or special functions
8
Alarm conditions
2
Control loops
2
Analog outputs, selectable with jumper: mA, VDC
1
Fan or lead lag modules, 1 to 3 fan speeds, up to 3 switching lead-lag stages each
2
Binary outputs with a normally open (NO) relays contact
1
Remote Enable: Activation of the controller based on signal and alarm conditions
1
Change Operation Mode: Switching occupied and unoccupied with control signals
1
Heat/Cool Change: Switching heating and cooling based on a control signal
1
Setpoint Compensation: Summer/winter compensation of setpoint
1
Economizer (free heating or cooling due to the condition of outside and room air)
-
Communication (if a communication module is available)
Copying complete parameter sets between run, default and external memory with
-
up to 4 memory locations (AEC-PM2)
Real time clock module with 48-hour power back up (keeps clock running during
1
power failure)
12
Time schedule programs for 7 days or annual switching events
Name
Read property - B
Read property multiple - B
Write property - B
Change of value - B
Device communication Control - B
Dynamic device binding - B
Dynamic object binding - B
Time synchronisation - B
UTC Time synchronisation - B
Reinitialize device - B
© Vector Controls LLC, USA
www.vectorcontrols.com
TCI2
P
D
S
RODUCT
ATA
HEET
Page 9-10