Salicru EQUINOX2 3001-S User Manual page 54

Single-phase solar inverters connected to the grid
Table of Contents

Advertisement

Available languages

Available languages

S/SX Models
EQX2 2001-S
EQX2 3001-S
EQX2 3002-S
EQX2 3002-SX
EQX2 4002-S
EQX2 4002-SX
EQX2 5002-S
EQX2 5002-SX
EQX2 6002-S
EQX2 6002-SX
EQX2 8002-SX
EQX2 10002-SX
Tab. 7. DC circuit breakers.
2.
DC connector assembly procedure.
a.
Select the suitable photovoltaic cable:
Type of cable
General
photovoltaic
cable
Tab. 8. Selecting the photovoltaic cable.
b.
Strip 7 mm. of the insulation sleeve of the DC cable,
as shown in Fig. 17:
7 mm
Fig. 17. Wire end stripping.
c.
Remove the connector from the accessory bag, as shown
in Fig. 18:
Fig. 18. Disassembling the connector.
d.
Insert the DC cable through the DC connector nut on the
metal terminal and press the terminal with professional
crimping pliers (pull the cable to check if the terminal is
well connected to the cable), as shown in Fig. 19:
54
Overvoltage
circuit breaker
Isolating
Fuses
If no light-
switch
ning rod is
installed
Fuses
1000Vdc
15A
Integrated
40kA
into the
600Vdc
Fuses
equipment
type II
1000Vdc
15A, 1
por string
Cross-section area
Range (mm
)
Recommended value (mm
2
2.5 - 4.0
Cable cross-section 2.5-4 mm
2
If lightning
rods are
installed
or there
is a high
probability
of lightning
5kA 1000Vdc
type I+II
e.
f.
)
2
4.0
Warning
voltage, check the polarity of the DC input cable, and make sure
that the voltage of each string is under the maximum voltage
specified in the "Tab. 16. Technical features.".
Fig. 21. Checking the polarity and voltage using a DC multimeter.
To ensure an optimal connection,
use an approved tool to crimp
the terminals.
Fig. 19. Crimping the cable.
Insert the positive and negative cables into the corre-
sponding positive and negative connectors, pull the DC
cable to make sure that the terminal is well connected
to the connector.
Use an open-end wrench to screw the nut all the way in
and make sure that the terminal is sealed well, as shown
in Fig. 20:
Use the special wrenches for
MC4 connectors to ensure
that the correct tightening
torque is applied, without
damaging the connectors.
Fig. 20. Using an open-end wrench.
Before assembling the DC connector, make sure that the
cable has the correct polarity.
Use a multimeter to measure the DC input string
SALICRU

Advertisement

Table of Contents
loading

Table of Contents