NOTE: ALL GAS FITTING MUST ONLY BE CARRIED OUT BY A QUALIFIED SERVICE PERSON.
1.
Waldorf Salamanders do not require an electrical connection, as they function totally on gas supply
only.
2.
It is essential that gas supply is correct for Salamander to be installed and that adequate supply
pressure and volume are available. The following checks should be made before installation:-
a. Gas Type appliance has been supplied
for, is shown on a coloured stickers located
above gas connection and next to rating
plate. Check that this is correct for gas
supply appliance is being installed for. Gas
conversion procedure is detailed in this
manual.
b. Supply Pressure required for this
appliance is shown in Specifications
section of this manual. Check gas supply to
ensure adequate supply pressure exists.
c. Input Rate of this appliance is stated on Rating Plate and in Specifications section of this manu-
al. Input rate should be checked against available supply line capacity. Particular note should
be taken if salamander is being added to an existing installation.
NOTE: It is important that adequately sized piping runs directly to connection joint on appliance
with as few tees and elbows as possible to give maximum supply volume.
3.
Fit gas regulator supplied, into gas supply line as close to appliance as possible. (Refer to
Specifications section for gas supply location dim ensions).
NOTE: Gas pressure regulator provided with this appliance is convertible between Natural Gas and
LPG as per 'Gas Conversion Section' in this manual.
Ensure regulator is converted to correct gas type that appliance will operate on.
Regulator outlet pressure is fixed ex-factory for gas type that regulator is converted to and
it is NOT to be adjusted.
Regulator connections are
Connection to appliance is
(Refer to Specifications section for gas supply location dimensions).
NOTE: A Manual Isolation Valve must be fitted to individual appliance supply line.
4.
Correctly locate appliance into its final operating position.
5.
Connect gas supply to appliance. A suitable jointing compound which resists breakdown action of
LPG must be used on every gas line connection, unless compression fittings are used.
6.
Check all gas connections for leakages using soapy water or other gas detecting equipment.
7.
Check gas operating pressure is as shown in Specifications section.
NOTE: Measure operating pressure at manifold test point with both burners operating at 'High
Flame' setting.
8.
Verify operating pressure remains correct.
1
/
" BSP female.
2
1
/
" BSP male.
2
D
O NOT USE A NAKED FLAME TO CHECK FOR GAS LEAKAGES
10
Rating Plate
Fig 5
.