M-system R7M-DAC16D-R Instruction Manual

Pnp discrete input & pnp transistor output module, 8 points each (modbus 115.2kbps)

Advertisement

Quick Links

INSTRUCTION MANUAL
PNP DISCRETE INPUT & PNP TRANSISTOR OUTPUT
MODULE, 8 points each
(Modbus 115.2kbps)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Discrete I/O module ............................................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
SEN TRONIC
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 40mA
■ GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply, input and output signal for safety.
• Before you remove the terminal block or mount it, turn
off the power supply, input and output signal for safety.
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure to close the terminal cover for safety.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet
056 222 38 18
mailbox@sentronic.com
AG
R7M-DAC16D
MODEL
EM-7803-AL Rev.4 P. 1 / 8
www.sentronic.com

Advertisement

loading

Summary of Contents for M-system R7M-DAC16D-R

  • Page 1 (Modbus 115.2kbps) BEFORE USE ..POINTS OF CAUTION Thank you for choosing M-System. Before use, please check ■ CONFORMITY WITH EU DIRECTIVES contents of the package you received as outlined below. • The equipment must be mounted inside the instrument If you have any problems or questions with the product, panel of a metal enclosure.
  • Page 2: Component Identification

    R7M-DAC16D COMPONENT IDENTIFICATION SIDE VIEW FRONT VIEW (A) Status Indicator LED 1 2 3 4 5 6 7 8 (B) Node Address Setting Rotary SW 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 (C) Baud Rate Setting Rotary SW CNFG.
  • Page 3 R7M-DAC16D ■ POWER SUPPLY, MODBUS TERMINAL ASSIGNMENT ■ TERMINATING RESISTOR To use the terminating resistor, turn the switch ON, and OFF to invalidate. DG +24V (Factory setting: OFF) ■ EXTENSION MODULE (1) DB – Combinations with all extension modules are available. (2) SLD Shield (3) FG...
  • Page 4: Terminal Connections

    R7M-DAC16D TERMINAL CONNECTIONS Connect the unit as in the diagram below. ■ EXTERNAL DIMENSIONS unit: mm (inch) 115 (4.53) 17 (.66) 54 (2.13) DIN RAIL 35 mm wide 10 11 12 13 15 16 17 18 30 (1.18) [5 (.20)] 6 (.24) 6 (.24) 7–M3 SCREW...
  • Page 5: Communication Cable Connections

    R7M-DAC16D COMMUNICATION CABLE CONNECTIONS ■ MASTER CONNECTION Host PC Remote Unit Remote Unit TERMINATOR TERMINATOR Tx+/Rx+ Tx–/Rx– Rx– Be sure to connect the terminating resistor included in the product package to the unit at both ends of transmission line. The terminator must be connected across DA and DB. The Host PC can be located other than at the extreme ends of transmission line.
  • Page 6 R7M-DAC16D I/O DATA DESCRIPTIONS ■ INPUT • Momentary Output Mode INPUT DATA STATE OUTPUT DATA STATE One-shot output One-shot output ---- ---- Unused One-shot output One-shot output ---- ---- Unused One-shot output One-shot output ---- ---- Unused One-shot output One-shot output ---- ---- Unused...
  • Page 7 R7M-DAC16D MODBUS FUNCTION CODES & SUPPORTED CODES ■ Data and Control Functions CODE NAME Read Coil Status Digital output from the slave (read/write) Read Input Status Status of digital inputs to the slave (read only) Read Holding Registers General purpose register within the slave (read/write) Read Input Registers Collected data from the field by the slave (read only) Force Single Coil...
  • Page 8: Wiring Instructions

    R7M-DAC16D WIRING INSTRUCTIONS ■ SCREW TERMINAL Torque: 0.5 N·m ■ SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size. Spade tongue type is also applicable. Applicable wire size: 0.25 to 1.65 mm (AWG 22 to 16) Recommended manufacturer: Japan Solderless Terminal MFG.