M-system R7 Series Instruction Manual

Discrete input extension module, 16 points, ethernet modbus/tcp
Hide thumbs Also See for R7 Series:

Advertisement

Quick Links

INSTRUCTION MANUAL
DISCRETE INPUT EXTENSION MODULE, 16 points
(Ethernet Modbus/TCP)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Discrete input extension module ..................................... (1)
■ MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrat-
ed in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 20mA
■ GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for sat-
isfying complete performance described in the data sheet.
SEN TRONIC
COMPONENT IDENTIFICATION
■ DISCRETE INPUT STATUS INDICATOR LED
Discrete input extension modules have LED indicators
showing input signal status.
Contact ON: LED ON
Contact OFF: LED OFF
■ INPUT TERMINAL ASSIGNMENT
NO.
1
2
3
4
5
6
7
8
9
056 222 38 18
mailbox@sentronic.com
AG
R7E-EA16
MODEL
Discrete Input Status Indicator LED
10 11 12 13
1
2
3
4
5
10
11
12
13
14
15
NC
X1
X3
X5
X7
1
2
3
4
5
6
COM
X0
X2
X4
X6
X8
ID
FUNCTION
NO.
COM
Common
10
X0
Input 0
11
X2
Input 2
12
X4
Input 4
13
X6
Input 6
14
X8
Input 8
15
XA
Input 10
16
XC
Input 12
17
XE
Input 14
18
EM-7807-I Rev.2
www.sentronic.com
R7E-EA16
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
14
15 16 17 18
6
7
8
9
Input Terminals
16
17
18
X9
XB
XD
XF
7
8
9
XA
XC
XE
ID
FUNCTION
NC
No Connection
X1
Input 1
X3
Input 3
X5
Input 5
X7
Input 7
X9
Input 9
XB
Input 11
XD
Input 13
XF
Input 15
P. 1 / 3

Advertisement

loading

Summary of Contents for M-system R7 Series

  • Page 1 (Ethernet Modbus/TCP) BEFORE USE ..COMPONENT IDENTIFICATION Thank you for choosing M-System. Before use, please check Discrete Input Status Indicator LED contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
  • Page 2 R7E-EA16 CONNECTING THE EXTENSION MODULE 1) Remove the extension connector cover located at the side of the basic module. 2) Connect the extension module. 3) Mount the combined module on a DIN rail. EXTERNAL DIMENSIONS unit: mm (inch) 17 (.66) 54 (2.13) 11.5 94 (3.70)
  • Page 3 R7E-EA16 CONNECTION DIAGRAM WIRING INSTRUCTIONS Connect the unit as in the diagram below. ■ SCREW TERMINAL Torque: 0.5 N·m ■ SOLDERLESS TERMINAL mm (inch) Refer to the drawing below for recommended ring tongue terminal size. Spade tongue type is also applicable. Solder- less terminals with insulation sleeve do not fit.