INSTRUCTION MANUAL
DISCRETE INPUT EXTENSION MODULE, 16 points
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Discrete input extension module ........................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V AC rating: 24V ±10%, 50/60 Hz, approx. 30mA
24V DC rating: 24V ±10%, approx. 20mA
■ GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and input signal for safety.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ FUNCTIONAL BLOCK SETTING
• Functional blocks regarding the extension module are set
by the basic module. Refer to the instruction manual for
the basic module for detailed information.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet
SEN TRONIC
(L
W
)
ON
ORKS
056 222 38 18
mailbox@sentronic.com
AG
MODEL
COMPONENT IDENTIFICATION
Discrete Input Status Indicator LED
10 11 12 13
1
2
3
■ DISCRETE INPUTS STATUS INDICATOR LED
Used to show discrete input signal status.
ON
: LED ON
OFF
: LED OFF
■ INPUT TERMINAL ASSIGNMENT
10
11
12
13
14
NC
X1
X3
X5
1
2
3
4
5
COM
X0
X2
X4
X6
NO.
ID
FUNCTION
1
COM
Common
2
X0
Input 0
3
X2
Input 2
4
X4
Input 4
5
X6
Input 6
6
X8
Input 8
7
XA
Input 10
8
XC
Input 12
9
XE
Input 14
www.sentronic.com
R7L-EA16
0 1 2 3 4 5 6 7 8 9 A B C D E F
14
15 16 17 18
4
5
6
7
8
9
Input Terminals
15
16
17
18
X7
X9
XB
XD
XF
6
7
8
9
X8
XA
XC
XE
NO.
ID
FUNCTION
10
NC
No Connection
11
X1
Input 1
12
X3
Input 3
13
X5
Input 5
14
X7
Input 7
15
X9
Input 9
16
XB
Input 11
17
XD
Input 13
18
XF
Input 15
EM-7804-I Rev.2 P. 1 / 3

Advertisement

loading

Summary of Contents for M-system R7 Series

  • Page 1 MODEL ORKS BEFORE USE ..COMPONENT IDENTIFICATION Thank you for choosing M-System. Before use, please check Discrete Input Status Indicator LED contents of the package you received as outlined below. If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
  • Page 2 R7L-EA16 CONNECTING THE EXTENSION MODULE 1) Remove the extension connector cover located at the side of the basic module. 2) Connect the extension module. 3) Mount the combined module on a DIN rail. TERMINAL CONNECTIONS Connect the unit as in the diagram below. ■...
  • Page 3 R7L-EA16 ■ CONNECTION DIAGRAM WIRING INSTRUCTIONS ■ SCREW TERMINAL Torque: 0.5 N·m ■ SOLDERLESS TERMINAL Refer to the drawing below for recommended ring tongue terminal size. Spade tongue type is also applicable. Applicable wire size: 0.25 to 1.65 mm (AWG 22 to 16) Recommended manufacturer: Japan Solderless Terminal MFG.