M-system R7L-TS4-R Instruction Manual page 17

Thermocouple input module, 4 points (lonworks)
Table of Contents

Advertisement

■ FUNCTIONAL BLOCK: fbDOEX[0...7]
• Network Properties
TYPE
NETWORK
{ Range }
VARIABLE
{ Default }
{SNVT_switch}
nviDOEX1
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
{SNVT_switch}
nviDOEX2
{0.0 0}, {100.0 1}, {Invalid}
{0.0 0}
• Configuration Properties
CONFIGURATION
NETWORK
PROPERTY
VARIABLE
SCPTdirection
----
SCPTpwrUpState
nviDOEX1
SCPTpwrUpState
nviDOEX2
SEN TRONIC
EXPLANATIONS
Turns on or off Y0, Y2, Y4, Y6, Y8, YA, YC, YE of the extension module
depending upon this input.
100.0 1 : ON
Other : OFF
Turns on or off Y1, Y3, Y5, Y7, Y9, YB, YD, YF of the extension module
depending upon this input.
100.0 1 : ON
Other : OFF
TYPE
{ Range }
EXPLANATIONS
{ Default }
{SNVT_state}
Bit 1: Output held or not at power off
{0 or 1}
0 : OFF at the power startup
{0,0,0,0,0,0,0,0,
1 : Outputs the held status at the power startup
0,0,0,0,0,0,0,0}
Bit 0, Bit 2 through 15 : Invalid
{SNVT_switch}
{0.0 0}, {100.0 1},
Set value applied at nviDOEX1 when the power supply is
{Invalid}
turned on.
{0.0 0}
{SNVT_switch}
{0.0 0}, {100.0 1},
Set value applied at nviDOEX2 when the power supply is
{Invalid}
turned on.
{0.0 0}
056 222 38 18
mailbox@sentronic.com
AG
R7L-TS4
EM-7804-B Rev.8 P. 17 / 19
www.sentronic.com