Core Power Solutions (DV2-C16 Models)
Installing the Batteries
•
•
•
The following are our recommended Battery Installation Practices. These supplement the
specific installation instructions of the relevant battery manufacturer.
Battery Installation Practices
General
Do not wear a synthetic dust-coat or overalls. Synthetic fabrics can hold a static electric
•
charge, creating sparks during discharge.
Remove rings, wristwatch and other metal jewelry that might be exposed to battery
•
terminals, before installing batteries.
Only use a clean soft damp cloth for cleaning the batteries. Do not use cleaning
•
detergents or chemicals.
Flooded cell and VRLA lead acid batteries can emit explosive gases and must be installed
•
with adequate ventilation. Refer to the battery manufacturer or supplier for advice on
minimum ventilation levels.
Switch off all battery circuit breakers and/or remove all battery fuses.
•
Unpacking and Inspecting the Batteries
Unpack the batteries and inspect them carefully for leaks, corrosion and possible
•
damage. Report any damage or other battery related problems immediately to the
battery supplier. Do not use damaged batteries.
Do not remove the factory-fitted transit insulation covers from the batteries until access
•
to the battery terminals is required.
Interconnecting the Batteries
Only terminate battery cables and interconnecting bars after confirming that the
•
termination will not create a short circuit.
Always use insulated tools.
•
Always tighten battery terminal bolts according to the battery manufacturer's
•
specification. Failing to do so can cause erratic battery performance, possible damage to
the batteries, and/or personal injury.
Do not place tools, loose cables, or metal objects (such as interconnecting bars) on top of
•
batteries.
Do not drop tools, loose cables, or metal objects onto intercell connections or terminals.
Installation procedure
Step 1 - Install the batteries
Follow the battery supplier's/manufacturer's installation instructions.
36
Always check that the battery cables have been terminated to the correct system
polarity BEFORE connecting the batteries or closing the battery disconnect
device.
Connecting batteries to the system with incorrect system polarity will void all
warranty claims.
See Warnings.