The I-component refers to the reset time of a control. The integral component has the effect of
moving the room temperature slowly toward, and ultimately reaching, the setpoint value.
Depending on the type of system used, the reset time has to have different values. In general,
the more inactive the overall system, the greater the reset time.
Note
This parameter is only available when "Control value type" parameter is set
either on "PI continuous, 0 – 100%", "PI PWM, On/Off" or "Fan coil". In addition,
the "Heating type" parameter must be set on "Free configuration".
Options:
This parameter enables additional functions and communication objects, e.g. "Basic stage
heating".
Note
Only available when the "Extended settings" parameter under "Heating control"
is set on "Yes".
Options:
This parameter enables the "Status heating" communication object.
Options:
The mode of the control value can be used to adapt the control value to de-energized opened
(normal) or de-energized closed (inverse) valves.
Normal: Value 0 means "Valve closed".
Inverse: Value 0 means "Valve open".
Description of application and parameters
Setting option between 0 - 255
No
Yes
No
Yes
Normal
Inverse
Application program
│39