With the "Threshold value / Hysteresis" application, value telegrams can be received on an input
communication object and compared with threshold values specified in the device.
Predefined values are sent out on the "Output" communication object if the upper threshold is
exceeded or the lower threshold drops below the set value. The size of the object can be
adjusted for different applications.
The function can be temporarily blocked via an enable object.
If the value of the lower threshold lies above the value for the upper threshold, the function is
not executed.
Threshold value / hysteresis objects
No.
Object name
0
Input (1-byte 0 - 100%)
Input (1-byte 0 - 255)
Input (2-byte float)
Input (2-byte signed)
Input (2-byte unsigned)
Input (4-byte float)
Input (4-byte signed)
Input (4-byte unsigned)
1
Output (1 bit)
Output (1-byte 0 - 100%)
Output (1-byte 0 - 255)
2
Enable
Description of application and parameters
Data type
1 byte EIS6 / DPT 5.001
1 byte EIS14 / DPT 5.010
2 byte EIS5 / DPT 9.xxx
2 byte EIS10 / DPT 8.001
2 byte EIS10 / DPT 7.001
4 byte EIS9 / DPT 14.xxx
4 byte EIS11 / DPT 12.001
4 byte EIS11 / DPT 13.001
1 bit EIS1 / DPT 1.001
1 byte EIS6 / DPT 5.001
1 byte EIS14 / DPT 5.010
1 bit EIS1 / DPT 1.001
Application program
Flags
C, W
C, W
C, W
C, W
C, W
C, W
C, W
C, W
C, T
C, T
C, T
C, W