Completing The Test - ABB REL 505-C1 2.3 Series Installation And Commissioning Manual

Overcurrent protection terminal
Table of Contents

Advertisement

15.1.2
15.2
92
Scheme communication logic for residual
overcurrent protection (EFC)
11. Switch on the fault current (110% of the setting) and wait long-
er than the set value tCoord.
No EFC--TRIP signal should appear.
12. Switch off the fault current and the polarising voltage.
13. Reset the EFC--BLOCK digital input.
Permissive scheme
Procedure
1.
Inject the polarising voltage 3U0 to 5% of Ub and the phase
angle between voltage and current to 65°, the current lagging
the voltage.
2.
Inject current (65° lagging the voltage) in one phase to about
110% of the setting operating current, and switch off the cur-
rent with the switch.
3.
Switch on the fault current (110% of the setting) and wait long-
er than the set value tCoord.
No EFC--TRIP signal should appear, and the EFC--CS binary out-
put should be activated.
4.
Switch off the fault current.
5.
Activate the EFC--CR binary input.
6.
Switch on the fault current (110% of the setting) and measure
the operating time of the EFC logic.
Use the EFC--TRIP signal from the configured binary output to
stop the timer.
7.
Compare the measured time with the set value tCoord.
8.
Activate the EFC--BLOCK digital input.
9.
Switch on the fault current (110% of the setting) and wait long-
er than the set value tCoord.
No EFC--TRIP signal should appear.
10. Switch off the fault current and the polarising voltage.
11. Reset the EFC--CR binary input and the EFC--BLOCK digital
input.

Completing the test

Continue to test another function or complete the test by setting the test mode to off.
Chapter 10
Verifying settings by secondary
injection

Advertisement

Table of Contents
loading

Table of Contents