Completing The Test - ABB REL 505-C1 2.3 Series Installation And Commissioning Manual

Overcurrent protection terminal
Table of Contents

Advertisement

19.2
Two step time delayed directional phase
overcurrent protection (TOC3)
2.
Slowly decrease the impedance angle to find the operating
value according to figure 9.
3.
Compare the result of the measurement with the set value.

Completing the test

Continue to test another function or complete the test by setting the test mode to off.
Chapter 10
Verifying settings by secondary
injection
101