3.3
46
Downloading settings and configuration
from a PC

Downloading the configuration and setting files

When downloading a configuration to the REx 5xx terminal with the CAP 531 config-
uration tool, the terminal is automatically set in configuration mode. When the terminal
is set in configuration mode, all functions are blocked. The red LED on the terminal
flashes, and the green LED is lit while the terminal is in the configuration mode.
When the configuration is downloaded and completed, the terminal is automatically set
into normal mode. For further instructions please refer to the users manuals for
CAP 535 and PST.
Setting and configuring the terminal