ABB REL 505-C1 2.3 Series Installation And Commissioning Manual page 92

Overcurrent protection terminal
Table of Contents

Advertisement

86
Monitoring of DC analogue
measurements
4.
Check the operating monitoring levels by changing the mag-
nitude of input current and observing the operation of the cor-
responding output relays.
The output contact changes its state when the changes in the input
measuring quantity are higher than the set values RMAXAL, HI-
WARN, HIALARM, or lower than the set values LOWWARN,
LOWALARM, RMINAL.
5.
Continue to test another function or complete the test by set-
ting the test mode to off.
Chapter 10
Verifying settings by secondary
injection