Overcurrent protection terminal
Table of Contents

Advertisement

Overview
Chapter 10
Verifying settings by secondary
injection
All used setting groups should be tested.
Note!
This terminal is designed for a maximum continuous current of four times the nominal
current.
Note!
Please observe the measuring accuracy of the terminal, the test equipment and the an-
gular accuracy for both of them.
Note!
Please consider the configured logic from the function block to the output contacts
when measuring the operate time.
53