Preparing for test
Test/TestMode/DisturbReport
Table 3: Disturbance report settings
Operation Disturb-
Summary
Off
Off
Off
On
On
On or Off
Then the results are...
Disturbances are not stored.
LED information is not displayed on the HMI and not
stored.
No disturbance summary is scrolled on the HMI.
Disturbances are not stored.
LED information (yellow - start, red - trip) are displayed
on the local HMI but not stored in the terminal.
Disturbance summary is scrolled automatically on the
local HMI for the two latest recorded disturbances, until
cleared.
The information is not stored in the terminal.
The disturbance report works as in normal mode.
Disturbances are stored. Data can be read from the local
HMI, a front-connected PC, or SMS.- LED information
(yellow - start, red - trip) is stored.
The disturbance summary is scrolled automatically on
the local HMI for the two latest recorded disturbances,
until cleared.
All disturbance data that is stored during test mode
remains in the terminal when changing back to normal
mode.
Chapter 10
Verifying settings by secondary
injection
59