9.4
High speed binary output logic (HSBO)
Procedure
1.
Apply faults according to table 7. Trip and carrier send out-
puts should appear as indicated (with YES).
2.
Remove applied signals.
3.
Set the terminal in normal service.
Table 7: Output signals for different fault types
Fault type
Signal
L1
HSBO-TRL1
YES
HSBO-TRL2
HSBO-TRL3
HSBO-CSL1
HSBO-CSL2
HSBO-CSL3
HSBO-CSMPH

Completing the test

Continue to test another function or complete the test by setting the test mode to off.
L2
L3
L1,L2
YES
YES
YES
YES
Chapter 10
Verifying settings by secondary
L2,L3
L3,L1
YES
YES
YES
YES
injection
L1,L2,L3
YES
YES
YES
81