ABB REL 505-C1 2.3 Series Installation And Commissioning Manual page 70

Overcurrent protection terminal
Table of Contents

Advertisement

4.2.2
64
Current reversal and weak end infeed
logic for residual
overcurrent protection (EFCA)
3.
Activate the EFCA-CRL binary input.
No EFCA-ECHO and EFC--CS should appear.
4.
Abruptly reverse the current to 65° lagging the voltage, to op-
erate the forward directional element.
No EFCA-ECHO and EFC--CS should appear.
5.
Switch off the current and check that the EFCA-ECHO and
EFC--CS appears on the corresponding binary output or on
the local HMI unit, about 200 ms after resetting the directional
element.
6.
Switch off the EFCA-CRL binary input.
7.
Activate the EFCA-BLOCK binary input.
8.
Activate the EFCA-CRL binary input.
No EFCA--ECHO and EFC--CS should appear.
9.
Switch off the polarising voltage and reset the EFCA-BLOCK
and EFCA-CRL binary input.
If setting WEI=Trip
Procedure
1.
Inject the polarising voltage 3U0 to about 90% of the setting
(Ugr) operating voltage.
2.
Activate the EFCA-CRL binary input.
No EFCA-ECHO, EFC--CS and EFCA-TRWEI outputs should
appear.
3.
Increase the injected voltage to about 110% of the setting
(Ugr) operating voltage.
4.
Activate the EFCA-CRL binary input.
5.
Check that the EFCA-ECHO, EFC--CS and EFCA-TRWEI ap-
pears on the corresponding binary output or on the local HMI
unit.
6.
Reset the EFCA-CRL binary input.
7.
Activate the EFCA-BLOCK binary input.
8.
Activate the EFCA-CRL binary input.
No EFCA-ECHO, EFC--CS and EFCA-TRWEI outputs should
appear.
9.
Reset the EFCA-CRL and EFCA-BLOCK binary input.
Chapter 10
Verifying settings by secondary
injection