Operation Pi Pressure/Cop Mode - S&P CAB ECOWATT PLUS Manual

Table of Contents

Advertisement

Available languages

Available languages

FACTORY SETTING?
NO
EN
MODE
<PI PRESSURE OK
Operation: depending on mode selected, displayed parameters will be specifi c to each one. Ending "RTC" modes are only in
combination with programming schedule TIMER RTC accessory.

6.6.3. Operation PI PRESSURE/COP mode

In section 5 we have described that the fan comes from factory ready to work in constant pressure mode. However, it is also
possible to connect an external pressure transducer (0-10V or 4-20mA) that should be connected to J5 or J6 terminals.
After selecting the operating PI PRESSURE/COP mode, you can confi gure following parameters:
MIN-OUTPUT
<
20%
MAX-OUTPUT
<
100%
46
Pressing on "YES", it is reloaded factory settings
SI
NO
OK
OK
OK
OK
MODE
PROP.+RTC
Operation PI PRESSURE/COP mode
Press
output parameter to the motor
OK
OK
OK
Press
output parameter to the motor
OK
OK
OK
MODE
MODE
PI VOLUME
PROPORT.
MODE
MODE
PIPRESS+RTC
PIVOLUME+RTC
or
to manually modify the minimum
or
to manually modify the maximum
MODE
MIN-MAX
MODE
MIN-MAX+RTC