20. Mounting methods

By means of appropriate mounting
accessories the standard IED case for the 615
series IED can be flush mounted, semi-flush
mounted or wall mounted. The flush
mounted and wall mounted IED cases can
also be mounted in a tilted position (25°)
using special accessories.
Further, the IEDs can be mounted in any
standard 19" instrument cabinet by means of
19" mounting panels available with cut-outs
for one or two IEDs. Alternatively, the IED
can be mounted in 19" instrument cabinets
by means of 4U Combiflex equipment frames.
For the routine testing purposes, the IED
cases can be equipped with test switches,
IECA070900 V2 EN
Figure 12. Flush mounting
21. IED case and IED
plug-in unit
For safety reasons, the IED cases for current
measuring IEDs are provided with
automatically operating contacts for short-
circuiting the CT secondary circuits when a
IED unit is withdrawn from its case. The IED
case is further provided with a mechanical
type RTXP 18, which can be mounted side by
side with the IED cases.
Mounting methods:
• Flush mounting
• Semi-flush mounting
• Semi-flush mounting in a 25° tilt
• Rack mounting
• Wall mounting
• Mounting to a 19" equipment frame
• Mounting with a RTXP 18 test switch to a
19" rack
Panel cut-out for flush mounting:
• Height: 161.5±1 mm
• Width: 165.5±1 mm
IECA070903 V2 EN
Figure 13. Semi-flush
mounting
coding system preventing current measuring
IED units from being inserted into a IED case
for a voltage measuring IED unit and vice
versa, i.e. the IED cases are assigned to a