Overvoltage Unit; Undervoltage Unit - ABB REU 523 Manual

Combined overvoltage and undervoltage relay
Hide thumbs Also See for REU 523:
Table of Contents

Advertisement

Application
Design
2
Combined overvoltage and undervoltage
relay
The over and undervoltage relay REU 523 is
a secondary relay which is connected to the
voltage transformers of the object to be pro-
tected. The over and the undervoltage unit
continuously measure the fundamental wave
of the phase-to-phase voltages of the object.
On detection of a fault, the relay will start,
trip the circuit breaker, provide alarms, record
fault data etc., in accordance with the applica-
tion and the configured relay functions.
The overvoltage unit includes low-set stage
U> and high-set stage U>> and the undervolt-
age unit low-set stage U< and high-set stage
U<<. The high-set undervoltage stage can
The relay includes: a high-set and low-set
overvoltage unit, a high-set and low-set und-
ervoltage unit and a circuit-breaker failure
protection unit. Further, the relay includes an
HMI module, a self-supervision system and a
disturbance recorder.

Overvoltage unit

When the voltage values exceed the set start
value of low-set stage U>, the overvoltage
unit will start to deliver a start signal after a ~
60 ms' start time. When the set operate time
at definite-time characteristic or the calcu-
lated operate time at inverse definite mini-
mum time (IDMT) characteristic elapses, the
overvoltage unit will deliver a trip signal.
When the voltage values exceed the set start
value of high-set stage U>>, the overvoltage
unit will start to deliver a start signal after a ~
50 ms' start time. When the set operate time
at definite-time characteristic or the calcu-
lated operate time at IDMT characteristic
elapses, the overvoltage unit will deliver a
trip signal.
The low-set and the high-set stage of the
overvoltage unit may be assigned either a def-
inite-time or an IDMT characteristic. When
the IDMT characteristic is chosen, two
time/voltage curve groups, A and B, are
available.
It is possible to block the start and the trip-
ping of an overvoltage stage by applying an
external binary input signal to the relay.
High-set stage U>> can be set out of opera-
tion. This state will be indicated by three
dashes "---" on the LCD and by "999" when
the set start current value is read via serial
communication.
alternatively be set to evaluate the positive-
phase-sequence voltage. In addition, the high-
set undervoltage stage can be configured to
evaluate only one instead of three phase-to-
phase voltages.
The protection functions are independent of
each other and have their own setting groups
and data recordings. The over and undervolt-
age functions use conventional voltage trans-
former measurement.
An output contact matrix allows start or trip
signals from the protection stages to be
routed to the desired output contact.

Undervoltage unit

When the voltage values fall below the set
start value of low-set stage U<, the undervolt-
age unit will start to deliver a start signal after
a ~ 80 ms' start time. When the set operate
time at definite-time characteristic or the cal-
culated operate time at IDMT characteristic
elapses, the undervoltage unit will deliver a
trip signal.
The high-set undervoltage stage can be set to
start and trip either based on conventional
undervoltage measurement or on the calcu-
lated positive-phase-sequence voltage, U1s.
Selecting either of these two will automati-
cally deseclect the other.
When the conventional protection mode is
selected for the high-set undervoltage stage
and the voltage values fall below the set start
value of high-set stage U<<, the undervoltage
unit will start to deliver a start signal after a
~50 ms' start time.
When the positive-phase-sequence protec-
tion mode is selected for the high-set under-
voltage stage and the calculated positive-
phase-sequence voltage value, U1s, falls
below the set start value of high-set stage
U<<, the undervoltage unit will start to
deliver a start signal after a ~50 ms' start
time. When the set operate time at definite-
time characteristic or the calculated operate
time at IDMT characteristic elapses, the und-
ervoltage unit will deliver a trip signal.
The low-set and the high-set stage of the und-
ervoltage unit may be assigned either a defi-
nite-time or an IDMT characteristic. When
the IDMT characteristic is chosen, one
time/voltage curve group, C, is available.
REU 523
1MRS 751123-MBG