Pulse signal:
The authorisation is released or terminated by
briefly activating the release input of the switching
contact. To change the setting from continuous sig-
nal to pulse signal, the configuration tool is re-
quired.
1 "6.5 Description of the configuration tool"
[} 21]
Electrical connection of the switching contact
ATTENTION
Material damage due to improper installation
Improper installation of the switching contact can
damage the product or lead to malfunctions. Ob-
serve the following requirements during the install-
ation:
u Select suitable cable routing to avoid interfer-
ence.
Enable input
12 V DC, 8 mA
Fig. 13: Schematic circuit diagram: Connection of an
external switching contact
u Install external switching contact.
u Strip the cable.
u Strip the conductors 10 mm.
u Connect the conductors to terminals 1 and 2
(XG1).
u Comply with the connection data for the enable
input.
1 "4 Technical data" [} 10]
Configuration
u Set DIP switch 3 on bank S1 to "ON".
20
XG1
1
NO
2
If a switching contact with pulse signal has been in-
stalled, an additional setting is required in the con-
figuration tool.
1 "6.5 Description of the configuration tool"
[} 21]
6.3

Switching on the product

The tasks described in this section may only
be carried out by a qualified electrician.
Requirement(s):
ü Product is installed correctly.
ü Product is not damaged.
ü The necessary protective devices are installed
in the upstream electrical installation in compli-
ance with the relevant national regulations.
1 "5.2.2 Protective devices" [} 13]
ü During the initial setting-up process, the product
was inspected in accordance with IEC 60364-6
and the applicable national regulations (e.g. in
Germany: DIN VDE 0100-600).
1 "6.4 Testing the product" [} 20]
u Switch on the power supply and check.
6.4

Testing the product

The tasks described in this section may only
be carried out by a qualified electrician.
u At initial start-up, test the product in accordance
with IEC 60364-6 and the applicable national
regulations (e.g. in Germany: DIN VDE
0100-600).
The test can be carried out in conjunction with the
MENNEKES test box and standard-compliant test
equipment. The MENNEKES test box simulates
vehicle communication. Test boxes are available as
an accessory from MENNEKES.