5.6.2 Power supply

Fig. 8: Power supply connection
u Strip the supply line.
u Strip the conductors 10 mm.
When routing the supply line, comply with
the permissible bending radius.
Single-phase operation
u Connect the conductors of the supply line to the
terminals L1, N and PE as per the terminal la-
belling.
u Comply with the connection data for the termin-
als.
1 "4 Technical data" [} 10]
To operate the product in single-phase mode, a
change in the configuration tool is also required
("Connected phases" parameter).
1 "6.5 Description of the configuration tool"
[} 21]
Three-phase operation
u Connect the conductors of the supply line to the
terminals L1, L2, L3 N and PE as per the terminal
labelling.
u Comply with the connection data for the termin-
als.
1 "4 Technical data" [} 10]

5.6.3 Shunt release

Requirement(s):
16
ü The shunt release is installed in the upstream
electrical installation.
1 "5.2.2 Protective devices" [} 13]
XG3
5
6
Fig. 9: Schematic circuit diagram: Connection of an
external shunt release
u Strip the cable.
u Strip the conductors 10 mm.
u Connect the conductors to terminals 5 and 6
(XG3).
Terminal
Connection
(XG3)
5
Shunt release
6
Power supply
n Max. 230 V AC or max. 24 V DC
n Max. 1 A
u Comply with the connection data for the switch-
ing output.
1 "4 Technical data" [} 10]
In the event of a fault (welded load contact),
the shunt release is activated and the
product is disconnected from the mains.