Orp Calibration Screens - Nalco 3D TRASAR Series Installation And Operation Manual

Table of Contents

Advertisement

Control
Alarm
Settings
Settings

4.10.5 ORP Calibration Screens

Select ORP from the Calibration menu and follow screen directions to per-
form calibration.
A
1-point calibration
It is best used to fine-tune your calibration to compensate for minor drift-
ing.
A
2-point calibration
major error has developed due to excessive fouling or probe degradation.
For a 1-point calibration
STEP 1 - Leave probe in tee with water flowing. Select 1-point calibration.
STEP 2 - Using a handheld instrument of known accuracy and calibration,
sample the process water and determine the ORP value.
STEP 3 - Enter this value.
For a 2-point calibration
STEP 1 - Select a 2-point calibration.
STEP 2 - Close the sample inlet, lower sensor outlet, and 3-way valves.
STEP 3 - Remove the ORP probe the tee.
STEP 4 - Swirl the probe in a beaker of clean, fresh ORP 200 mV buffer
solution
STEP 5 - After prompt, rinse probe well in clean DI water and wipe clean.
STEP 6 - Swirl probe in a beaker of clean, fresh 600 mV buffer solution
(P/N
460-S0933A.75). Press Continue.
STEP 7 - After successful calibration reinstall probe and open valves.
!
Technical Help
(630) 305-CHEM
Menu
Network
Preferences
utilizes the system water as the calibration point.
is best utilized when installing a new probe or if a
(P/N
460-S0932A.75). Press Continue.
If probe calibration is unsuccessful, check standards, wiring
connections, or handheld ORP meter for accuracy . Clean the
ORP probe tip and recalibrate.
521-OM0108.88
Copyright © 2009 Nalco Company
®
3D TRASAR
5500 - Installation & Operation Manual
Information
System
Info
Alarms
Actions
Manual
Relay
4-21