Ph Calibration Screens - Nalco 3D TRASAR Series Installation And Operation Manual

Table of Contents

Advertisement

Control
Alarm
Settings
Settings

4.10.4 pH Calibration Screens

Select pH from the Calibration menu and follow screen directions to
perform calibration:
A
1-point calibration
It is best used to fine-tune your calibration to compensate for minor drifting.
A
2-point calibration
major error has developed due to excessive fouling or probe degradation.
For a 1-point calibration
STEP 1 - Leave probe in tee with water flowing. Select 1-point calibration.
STEP 2 - Using a handheld instrument of known accuracy and
calibration, sample the process water and determine the pH
value.
STEP 3 - Enter this value.
For a 2-point calibration
STEP 1 - Select 2-point calibration.
STEP 2 - Close the sample inlet, lower sensor outlet, and 3-way valves.
STEP 3 - Remove the pH probe from the tee.
STEP 4 - Swirl the probe in a beaker of clean, fresh pH 7.0 buffer
solution
(P/N
STEP 5 - After prompt, rinse probe well in clean DI water and wipe clean.
STEP 6 - Swirl probe in a beaker of clean, fresh pH 10.0 buffer solution
(P/N
460-S0408.75). Press Continue.
STEP 7 - After successful calibration reinstall probe and open valves.
!
Technical Help
(630) 305-CHEM
Menu
Network
Preferences
utilizes the system water as the calibration point.
is best utilized when installing a new probe or if a
460-S0407.75). Press Continue.
If probe calibration is unsuccessful, check standards, wiring
connections, or handheld pH meter for accuracy . Soak probe
in standard extra 5-10 min or clean probe tip and recalibrate.
521-OM0108.88