Switch Setting Comparison - Mitsubishi MELSEC Q Series Handbook

Transition from melsec-a/qna (large type), ans/qnas (small type) series to q series
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

2
SERIAL COMMUNICATION MODULE REPLACEMENT

2.4 Switch Setting Comparison

(1) Comparison between A series and Q series
Switch name
Mode switch
Station number switch
SW11
SW12
SW13
to
SW15
SW16
SW17
Transmission
specification
switch
SW18
SW21
SW22
SW23
SW24
A series
AJ71UC24
Each of the interface modes' setting is
determined by the data communication
function to be used.
RS-232
0
Use not allowed
1
Dedicated
to
protocol
4
(format1 to 4)
Non-procedural
5
mode
to
or
8
bidirectional
mode
9
Non-procedural mode
A
to
Dedicated protocol (format1 to 4)
D
E
Use not allowed
F
Self-loopback test
The station number of the module for
when date communications is performed
using dedicated protocol is set.
The target interface of transmission
Main channel
processing and reception processing is
setting
set.
Data bit
The data bit length of the data to be
setting
transmitted/received is set.
Transmission
The transmission speed for when data is
speed setting
to be transmitted/received is set.
Parity bit
The parity bit ON/OFF of the data to be
enable/disable
sent/received is set.
setting
Even/odd parity
The type of parity bit to add to the data to
setting
be transmitted/received is set.
Stop
The stop bit length of the data to be
bit setting
transmitted/received is set.
Sum check
The sum check code presence in
enable/disable
dedicated protocol data communications
setting
is set.
Write during
Write during RUN enable/disable in
RUN enable/
dedicated protocol data communications
disable setting
is set.
computer link/
The function of computer link module to
multidrop link
be used is set.
selection
master/local
The station type for use of multidrop link
station setting
function is set.
:Compatible,
Description
Q series
QJ71C24N
QJ71C24N-R2
QJ71C24N-R4
RS-422/485
Non-procedural
mode
or
bidirectional
mode
-
Dedicated
protocol
(format1 to 4)
-
-
-
-
-
-
-
-
-
-
-
:Partial change required, ×:Incompatible
Compat-
Precautions for
Reference
ibility
replacement
Set the switch settings
in the GX Developer
PLC parameter
settings.
Refer to Section 2.4
*1
(3)
.
Section 2.7
There is no distinction
-
with the main channel
on the Q series.
Set the switch settings
in the GX Developer
PLC parameter
settings.
Refer to Section 2.4
*1
(3)
.
-
There is no multidrop
link function provided
for the Q series.
-
section
2
- 15