4. System Controller (SHA-KC64UG)
(b) Zone registration using the system controller (SHA-KC64UG)
In this case, you set all central addresses by the
system controller at once manually.
(1) Press the
and
for more than 4 seconds.
and CODE No. C1 will flash.
(2) After confirming that CODE No. C1 is displayed,
press the
button. Once in this mode, a change
takes place as shown at the right.
(3) Select the zone and group No. you want to set
with
and
If already set, press the
(4) Set the unit No. (indoor unit address) with
buttons, according to the zone registration table.
R.C. No. ..........................
Indoor unit No..................
(5) Press the
button.
GROUP No. turns ON and UNIT No. (indoor unit
address) changes from flashing to ON state.
UNIT No. is registered to selected ZONE No. and
GROUP No.
If you make a mistake, press the
reselect the ZONE, GROUP and UNIT No.
(6) Register the other UNIT Nos. in the same way by
following the steps (3) to (5).
(7) Finally, complete the registration by pressing the
button.
flashes for a few minutes, then turns OFF.
buttons at the same time
(GROUP) buttons.
buttons.
and
button
button
button and
If data is
registered,
the unit No.
is displayed.
For example, in the case Zone 3, Group No. 7
Unit No. (indoor unit address) 2-8
Unit No. 2-8 is registered to Zone 3, Group No. 7.
2-57
Remote Control Functions
If no data is
registered,
no number
is displayed.
Selected
group No. if
no data is
registered.
2