Sanyo MINI ECO-i XHX1252 Service Manual & Test Run Service Manual page 52

Hide thumbs Also See for MINI ECO-i XHX1252:
Table of Contents

Advertisement

3. Timer Remote Controller (RCS-TM80BG)
List of Simple Setting Items
Filter sign ON time
(filter lifetime)
Central control address
Fan speed when
heating thermostat is
OFF
Heating intake
temperature shift
Cooling-only
NOTE
• In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF
unless a vaporizing humidifier is used.
• Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
• Do not change any setting data that does not appear in this list.
0000
Not displayed
(The optimal setting for that model was set at the time of shipment.)
0001
150 hours
0002
2,500 hours
0003
5,000 hours
0004
10,000 hours
0005
Use the filter clogging sensor.
0001
Central control address 1
0002
Central control address 2
0003
Central control address 3
0064
Central control address 64
0099
No central control address set (setting at time of shipment)
Compressor ON
0000
MED 1 min., LO 3 min.
0
0
0
1
M
E
D
0
0
0
2
L
O
0004
MED 1 min., LO 3 min.
0
0
0
5
M
E
D
0
0
0
6
L
O
0000
No shift
Shifts intake temperature 2°F ( 1°C ) down.
0001
Shifts intake temperature 4°F ( 2°C ) down.
0002
Shifts intake temperature 6°F ( 3°C ) down.
0003
Shifts intake temperature 8°F ( 4°C ) down.
0004
Shifts intake temperature 10°F ( 5°C ) down.
0005
Shifts intake temperature 12°F ( 6°C ) down.
0006
0000
Normal (Setting at time of shipment)
0001
Cooling only
2-34
Remote Control Functions
Compressor OFF
LO
L
O
L
O
MED
M
E
D
M
E
D

Advertisement

Table of Contents
loading

Table of Contents