7. LonWorks Interface product Manual (SHA-LN16UAB)
Communications LED (Green)
COM
1
2
LD
LD001
LD002
X
X
Power OFF
X
Low
–––––
X
High
Flash writer writing in progress
X
O
Waiting for A/C unit initial communication
Low
X
A/C unit initial communication in progress
Low
Low
–––––
Low
High
LonWorks communication microcomputer error
Lo
w
O
EEPROM error
High
X
–––––
High
Low
–––––
High
High
–––––
High
O
–––––
O
X
Test run mode
O
Low
–––––
O
High
Version display in progress
O
O
Normal communications in progress
X: Not lit、Low: Low-speed flashing (once/second)
High: High-speed flashing, O: Constantly lit
Data LED (Red)
Data
LD
3 4 5 6 7 8
Communications
Data LED display meaning
LED
No LED lit
All LEDs lit
–––––
Displays the wait time (seconds) for A/C
unit initial communication.
Displays the A/C unit communications status
–––––
No LED lit
No LED lit
–––––
–––––
–––––
–––––
According to the test run mode specifications
–––––
According to the version display specifications
Displays the A/C unit communications status
COM: Communications
Display meaning
Display of A/C unit communications status
LD
Display meaning
Indoor unit
OFF: Waiting for initial communication
group
Low-speed flashing: Waiting for minimum
003
0
004
1
High-speed flashing: Initial communication in
005
2
006
3
ON: Normal communications in progress
Illuminates for 200 ms when data is output to the
007
LonWorks communicator.
Illuminates for 200 ms when data is output to the
008
indoor/outdoor communicator.
Diagram of External Dimensions
8-15/32
3-7/64
Product Specifications
LonWorks network
Connects to
FTT-10 A transceiver device
Power
Single-phase, AC 100-120V or 200-240V
Power
11 W max.
consumption
Service
Temp. 32-104°F (0-40°C), humidity 20 to 80%
environment
Indoor use only
conditions
External
Height × Width × Depth
dimensions
3-7/64 (in.) × 19-11/16 (in.) × 8-15/32 (in.)
Weight
Approx. 7.28 lb (3.3 kg)
2-127
Remote Control Functions
transmission interval
progress
(in.)
19-11/16