4.3 ERROR HISTORY - BuRNER CONTROL PHASE

Phase
Phase
Phase
No:
display
reference
code
1
TNB
Homerun
2
TLO
Homerun
3
TNN
Homerun
4
STY
Standby
5
STV
Standby
6
THL1
Startup
7
THL1A
Startup
8
TV
Startup
9
TBRE
Startup
10
TW1
Startup
11
TW2
Startup
12
TVZ
Startup
13
TSA1
Safety time
14
TSA2
Safety time
15
TI
Operation
16
MOD
Operation
17
THL2
Shutdown
18
THL2A
Shutdown
19
TN1
Shutdown
20
SAF
Error
21
STOE
Error
22
TNA
Shutdown
23
KT
Standby
24
TN2
Shutdown
Engineer
Phase description
Explanation
Permitted afterburn
Not relevant for the MAXXflo EVO
time
Permitted time with fan
Time after post purge when the air flap is still open as the fan
speed
speed runs down
Permitted time with fan
Time after post purge when the fan is permitted to run on
speed
No demand
No heat demand, burner is not active
Start prevention
Burner held until a temporary condition has been removed (e.g.
B2 sensor disconnected)
Fan ramp-up time to
Maximum fan ramp-up time for fan to reach pre-purge speed
ignition speed
Fan ramp-up time to
Maximum fan ramp-up time for fan to reach ignition speed
ignition speed
Pre-purging
Fan pre-purging phase
Fan adjustment
Maximum time required to reach ignition level after pre-purging
Waiting time
Maximum waiting time until the following functions complete:
- Internal safety tests
- Fan speed adjustment to ignition load
Waiting time
Fan speed adjustment to ignition load
Pre-ignition phase
Time before ignition (minimum 0.2 seconds)
1st safety time
First part of safety time with spark on and gas valve open
2nd safety time
Second part of safety time with spark off and gas valve open
Interval
Stabilisation of flame (5 seconds)
Control mode
Burner is modulating normally - Main phase of operation
Post purging
Post purging at last operating fan speed - Demand has been
turned off, gas valve will be closed
Post purging
Post purging at pre-purge fan speed - Demand has been turned
off, gas valve will be closed.
Post purging
Post purging at last operating fan speed - Demand has been
turned off, gas valve will be closed
Boiler error state
Certain types of error can force the heater control to jump to this
phase and all safety related outputs are deactivated. When the
condition returns to normal, this phase will be skipped and the
control will restart. This will avoid lockout and the need to reset.
Boiler error state
If the heater controls detect a system error that would drive the
heater into an unsafe state (i.e. lockout), the heater controls will
jump to this phase. Only an applied reset can resume operation.
Post purging at pre-
Last phase of fan post purge before the boiler controls go to
purge speed
standby phase.
Start prevention
Temporary start prevention condition becomes a permanent con-
dition after a period of time has elapsed.
Interruptable post
Interruptible post purging at last fan operation speed. If there is a
purging
new heat demand during the post purge period, post purging can
immediately be interrupted.