6.6 ERROR CODES

Error
Error Code Description
Code
20
Boiler temperature 1, sensor
error
26
Common fl ow temperature
sensor error
28
Flue gas temperature, sensor
error
40
Return temperature 1, sensor
error
50
DHW temperature 1, sensor
error
81
LPB short-circuit or no power
supply
82
LPB address collision
83
BSB short circuit
84
BSB address collision
98
Extension module 1, error
99
Extension module 2, error
100
More than one clock time
master
102
Clock master without power
reserve
105
Maintenance message
Maintenance
Diag.
Notes
Code
Other
Boiler fl ow sensor (B2) is outside normal limits
439
Boiler fl ow sensor (B2) is short-circuit
440
Boiler fl ow sensor (B2) is open-circuit
Any
Check connections or replace faulty sensor located on com-
mon fl ow pipe work up stand section (B10)
539
Flue gas sensor (B8) is short-circuit
543
540
Flue gas sensor (B8) is open-circuit
544
Other
Boiler return sensor (B7) is outside normal limits
441
Boiler return sensor (B7) is short-circuit
442
Boiler return sensor (B7) is open-circuit
Any
Check connections or replace faulty DHW tank sensor (B3)
Any
LPB Short circuit or no bus power supply. Check operation of
OCI345 modules and connecting cables
Any
LPB address duplicated on another Control PCB - Check ad-
dress of all control PCBs via parameter 6600
Any
No BSB communication or wires shorted - Check operation of
GUI or OZW672 (if fi tted)
Any
Two appliances connected through BSB (e.g. OZW672) have
the same allocation address. Change one of the appliances
address via parameter 6600
Any
AGU2.5 confi guration error - Check parameters
Any
AGU2.5 confi guration error - Check parameters
Any
Only one device should be set as the time master, check on
the GUI (parameter 6640) and any OZW672 connected (in
case of connection to an OZW672, this device should be the
master)
Any
The control PCB battery backup for the time clock has been
depleted following the restoration of power to the heater. If this
message has not cleared within 10 minutes of power being
turned on, turn the power off , wait 10 seconds and turn the
power on again. This message does not prevent the operation
of the heater in any way.
Any
Item requiring attention but not preventing appliance operation
(e.g. 12 Month service due). Check details of message on the
appliance Front GUI screen.
79