2.10 ERROR COdES (CONTINuEd)
Error
Error Code description
Code
217
Sensor error
317
Mains frequency outside per-
mitted range
322
Water press 3 too high
324
Input BX, same sensors
325
Input BX/extension module,
same sensors
327
Extension module, same
function
335
Sensor input BX21 without
function
336
Sensor input BX22 without
function
353
Cascade flow sensor B10
missing
384
Extraneous light
End user
diag.
Notes
Code
765
Ionisation current fault or short circuit. Check operation of ioni-
766
sation probe using parameter 8329 (menu - Diagnostics heat
generation). Ionisation probe may need replacing. Check electri-
cal supply to the heater and burner - pay special attention to the
earth circuit and supply to the heater.
275
The frequency (Hz) of the electrical supply is outside permitted
461
tolerance. Check electrical supply to heater.
85
Water pressure inside the appliance is too high for safe opera-
86
tion. Operation will automatically resume once water pressure
516
is at or below maximum levels. Check that the appliance flow is
565
not restricted or blocked, or the water isolator valves are shut
off.
110
BX sensor duplicated - Two sensor inputs have been defined
twice with the same sensor type (e.g. B3). Review last param-
eters programmed to remove duplication.
Any
BX expansion module 1 sensor duplicated - Two sensor inputs
have been defined twice with the same sensor type (e.g. B3).
Review last parameters programmed for the expansion module
to remove duplication.
Any
AGU2.5 extension module function duplicated - check param-
eter setup for the AGU2.5 extension module ("Configuration"
menu)
211
A sensor has been detected connected to BX21 of the AGU2.5
expansion module 1, but not defined. Define the sensor using
the parameters or remove the sensor if not required.
213
As above except the undefined sensor is connected to an
215
AGU2.5 expansion module. The AGU2.5 expansion module
should be defined as module 1 - Check the dip switches on the
front of the device are set correctly
Any
See Error 335 for guidance
Any
Check connections and configuration of common flow tempera-
ture sensor (B10), which is located at the feed into the tank on
the front, left, mid section of the appliance.
252
Ionisation current detected before whilst in standby mode.
393
Check ionisation current ("Diagnostics producer" parameter
8329). If the current present is greater than 0.61 whilst the
burner is in standby, turn off the gas supply to check gas valve
is closing completely. If current is still present, remove ionisation
probe and use a screwdriver to clear the opening through the
burner door before replacing the probe and testing again.
Persistent errors may indicate that the burner is only operational
for very short periods. Try increasing the switching differential by
at least 1
C (parameter 5024) to increase burner run time.
O
Other
Ionisation current detected during ignition phase before the gas
valve is opened.
22