4.5 COMPLETE PARAMETER LIST TABLE

PARAMETER DESCRIPTION
Time of day and date
1
Time & Date
5
Start of summertime
6
End of summertime
Operator section
20
Language
40
Used as
42
Assignment device 1
44
Operation zone 2
46
Operation zone 3
48
Warmer / cooler device 1
70
Software version
Time program 4 (water heater)
Set time program
576
Default values
Time program 5 (Q4 secondary return pump)
Set time program
616
Default values
dHW
1600
DHW operating mode
1610
Nominal setpoint
1612
Reduced setpoint
Example:
Engineer
FACTORY
NOTES
DEFAULT
-
Current time and date settings. These settings can be
changed.
-
Date of start for British Summer Time. An automatic one
hour adjustment will be made at 01:00 on this date. Please
remember that this date changes by a few days every year, so
adjustment of these dates at the start of the year is recom-
mended.
-
Date of start for British Winter Time. An automatic one hour
adjustment will be made at 01:00 on this date. Please re-
member that this date changes by a few days every year, so
adjustment of these dates at the start of the year is recom-
mended.
English
Change languages if required
Operator unit 1
Operator unit 1 only should be set
-
Has no effect on DHW operation
-
Has no effect on DHW operation
-
Has no effect on DHW operation
-
Has no effect on DHW operation
-
Current firmware version for this Graphical User Interface
(GUI)
Optimised for
Used to set the time program for DHW heating (can also be
BS EN 13302-1
set on the DHW water heater menu of the user screen) Follow
section 2.3 for instruction on how to set the time clock.
06:00 - 22:00
Reverts time clock settings to default values
daily
24 hours every
Used to set the time program for DHW secondary return. Fol-
day
low section 2.3 for instruction on how to set the time clock.
06:00 - 22:00
Reverts time clock settings to default values
daily
-
On or Standby (operation via switch on front of heater)
57
C - 60
C
Normal DHW set point (setpoint when activated within pro-
O
O
gram 4 times) - Up to Max of 65
10
C
This reduced temperature setpoint is active when the current
O
Optimised for
time is outside the water heating time program settings (time
EN13302-1
program 4).
1612
1610
Max setting
37
C
o
MAXXflo EVO