3.10 Commissioning

Ensure the Pump Switches are in the OFF position.
Connect Superchiller power supply lead to an appropriate 3 pin socket outlet and switch the
main power on. The condenser fan and agitator motor should start immediately. There is a 3-
minute delay from initial power on before the compressor starts.
The Power On and Waterbath > 5°C LED's on the front panel should be illuminated.
The Waterbath > 5°C LED should go out approximately after 60-90 minutes.
When the ice bank is fully formed (approx. 4 -5 hours) the compressors will cycle off, but the
agitator and fan will run continuously.
After the Superchiller has cycled off, place the Pump Switches to the ON position to activate
the carbonator and recirculation pumps.

3.11 Purge System

Progressively activate each dispensing valve or Bargun connected to the Superchiller systems
until an uninterrupted flow of soda, water (where applicable), and syrup pours from each
dispenser.

3.12 LED Display Panel

FUNCTION
POWER
LOW CO2
(OPTIONAL)
LOW H2O
(OPTIONAL)
CARBONATOR
TIMEOUT
WATERBATH > 5C
www.lancerbeverage.com
Hoshizaki Lancer reserve the right to change specifications without notice.
Images are for illustration purposes only as product may vary.
DESCRIPTION
Indicates connection to mains utility. Is the only LED lit under normal
operating conditions.
If equipped indicates CO2 pressure has dropped below 415 kPa (60 psi)
and in most cases indicates a depleted CO2 cylinder. Replace CO2
cylinder and check regulator set to 560 kPa (80 psi).
If equipped indicates incoming water pressure has dropped below 140
kPa (20 psi) for longer than 3 minutes and switched the pumps off.
Check incoming water supply for closed cocks, pinched or blocked lines,
dirty / clogged water filter etc.
The carbonator has run past its timeout setting (default = 5 minutes).
This may indicate a blockage, a water supply problem, broken pipe
downstream or other related issue. Find and repair the problem. Cycle
power at the wall to reset.
Should remain off during normal operations. If illuminated then either
there is an issue with the refrigeration, agitation or severe use over the
capacity of the chiller. Investigate and resolve the issue.