Analog Restore Output (Ao) Wiring; Analog Impedance And Other Information - Ebyte K62-DL20 User Manual

0/4 20ma analog transmission module
Table of Contents

Advertisement

Chengdu Ebyte Electronic Technology Co.,Ltd.
K62-DL20 User Manual

3.4.4 Analog restore output (AO) wiring

Figure 3-5 Receiver Wiring diagram
( The output is an active signal: constant current source output, the load resistance should be ≤500Ω)

3.4.5 Analog impedance and other information

(1) Analog input AI (Analog Input) related
1. Input source information: 0/4~20mA active analog signal, constant current source voltage should be ≥10V.
2. Error, accuracy, limit value: acquisition accuracy: ≤ ± 0.03mA; acquisition resolution: 0.001mA; input maximum
current Imax≤28mA, overcurrent may cause product damage.
3. The internal impedance of the product: 480 Ω
= 330 Ω
(current limiting protection resistance) + 150 Ω
(high-precision acquisition resistance).
(2) Related to analog output AO (Analog Output)
1. Output source information: 0/4~20mA active analog signal, constant current source output.
2. Error, precision, limit value, etc.: Output error: ≤±0.03mA. Output accuracy: 0.001mA. The load impedance should
be ≤500Ω, and active power supply should not be connected to avoid damage to the product.
3. Internal impedance of the product: constant current source voltage: 24V. Constant current source internal resistance:
500Ω.
(For the internal circuit structure diagram of the product, see "
Product Internal Circuit Structure Diagram
")
28
Copyright ©2012–2021,Chengdu Ebyte Electronic Technology Co.,Ltd.

Advertisement