Huawei SUN2000-4.95KTL-JPL1 User Manual page 85

Hide thumbs Also See for SUN2000-4.95KTL-JPL1:
Table of Contents

Advertisement

SUN2000-4.95KTL-JPL1
User Manual
Alarm
Alarm Name
ID
2037
Grid
Underfrequenc
y
2038
Unstable Grid
Frequency
Issue 05 (2023-02-17)
Alarm
Possible Causes
Severity
Major
Cause ID = 1
Power grid exception: The
actual power grid
frequency is lower than the
standard requirement for
the local power grid.
Major
Cause ID = 1
Power grid exception: The
actual grid frequency
change rate does not
comply with the local
power grid standard.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Troubleshooting
1. If the alarm occurs
occasionally, the power
grid may be abnormal
temporarily. The
SUN2000 automatically
recovers after detecting
that the power grid
becomes normal.
2. If the alarm occurs
frequently, check
whether the power grid
frequency is within the
allowed range. If not,
contact the local power
operator. If yes, modify
the grid underfrequency
protection threshold
through the mobile app,
SmartLogger, or NMS
with the consent of the
local power operator.
1. If the alarm occurs
occasionally, the power
grid may be abnormal
temporarily. The
SUN2000 automatically
recovers after detecting
that the power grid
becomes normal.
2. If the alarm occurs
frequently, check
whether the power grid
frequency is within the
allowed range. If not,
contact the local power
operator.