Huawei SUN2000-4.95KTL-JPL1 User Manual page 83

Hide thumbs Also See for SUN2000-4.95KTL-JPL1:
Table of Contents

Advertisement

SUN2000-4.95KTL-JPL1
User Manual
Alarm
Alarm Name
ID
2034
Grid
Overvoltage
Issue 05 (2023-02-17)
Alarm
Possible Causes
Severity
Major
Cause ID = 1
The grid voltage exceeds
the higher threshold or the
high voltage has lasted for
more than the value
specified by high voltage
ride-through (HVRT).
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Troubleshooting
1. If the alarm occurs
occasionally, the power
grid may be abnormal
temporarily. The
SUN2000 automatically
recovers after detecting
that the power grid
becomes normal.
2. If the alarm occurs
frequently, check
whether the power grid
voltage is within the
allowed range. If not,
contact the local power
operator. If yes, modify
the grid overvoltage
protection threshold
through the mobile app,
SmartLogger, or NMS
with the consent of the
local power operator.
3. Check whether the peak
voltage of the power
grid is too high. If the
alarm persists and
cannot be rectified for a
long time, contact the
power operator.
77