Alarm
Alarm Name
ID
2015
PV String Loss
2021
AFCI Check
Failure
2031
Short Circuit
Between Grid
Phase Wire and
PE
2032
Grid Failure
Issue 05 (2023-02-17)
Alarm
Possible Causes
Severity
Warning
Cause ID = 1
This alarm is generated
when the PV string status is
abnormal due to the
following conditions: a
single PV string is lost; both
2-in-1 PV strings are lost;
one of the 2-in-1 PV strings
is lost.
Major
The AFCI check fails.
Cause ID = 1, 2
● Cause ID 1: The AFCI
check circuit is
abnormal.
● Cause ID 2: The AFCI
circuit is faulty.
Major
The impedance of the
output phase wire to PE is
low or the output phase
wire is short-circuited to PE.
Major
Cause ID = 1
● The power grid
experiences an outage.
● The AC circuit is
disconnected or the AC
circuit breaker is OFF.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Troubleshooting
1. Check whether the
SUN2000 terminals are
properly connected.
2. Check whether the PV
string terminals are
properly connected.
3. If a 2-in-1 terminal is
used, check whether it is
normal.
Note: If the string
connection status is
manually configured, check
whether the configured
status is consistent with the
actual connection status.
Turn off the AC output
switch and DC input switch,
and then turn them on
after 5 minutes. If the
alarm persists, contact your
dealer or Huawei technical
support.
Check the impedance of
the output phase wire to
PE, locate the position with
low impedance, and rectify
the fault.
1. Check the AC voltage.
2. Check whether the AC
circuit is disconnected or
the AC circuit breaker is
OFF.