MEGA.V2 250: TECHNICAL SPECIFICATIONS FOR THE SYSTEM CONTROLLER
Display
Other indicators
Analog input channels
Real-time clock (RTC)
Power meter
Volt-free outputs (dry contacts)
Output dry contacts
Communication ports
Communication protocols
Communications with system modules
Events log
System operation without controller
On-screen parameters
RTC operation without power
Power requirements
Remote indication panel capability
MegaV2 250 Installation Guide, Release 2.2
G
E
I
AMATRONIC
LECTRONIC
NDUSTRIES
LCD flat panel, touch-sensitive
Audible alarm
4 input dry contacts (N.O. / N.C.)
Yes, with backup
kVA, kW, PF
6 outputs, rated 48 V / 1 A
Ac failure
Dc failure
UPS module(s) failure
Load on bypass
Battery test failure
Over/under temperature
Overload
(Each system alarm type can be routed to the dry
contact of your choice.)
Serial, Ethernet, USB
RS232, RS485, TCP/IP, SNMP, Modbus
Serial, isolated
500 events
Unchanged
Load bar-graph
3-phase voltages
3-phase currents
Battery voltage
Status of each UPS module
Static-switch parameters and status
Battery sensor temperature
Indefinitely
3 × 400 Vac and 405 Vdc