Specifications - Honeywell FS24X Plus User Manual

Advanced multi-spectrum 3ir flame detector
Table of Contents

Advertisement

Specifications

Temperature:
Humidity:
Field of View (Conical) for
Standard Mount:
EN 54-10 Field of View:
Test Lamp:
Operating Voltage:
Power Consumption:
Honeywell®FS24X Plus™ | User Manual
Operating Temperature (ATEX/IECEx):
Storage Temperature (ATEX/IECEx):
Operating Temperature (North America):
Storage Temperature (North America):
0 to 99% relative humidity, can withstand 100% condensing
humidity for short periods of time.
The detector has a cone of view for all standard mounts of 90°
(left 45°, right 45°, up 40°, down 50°) horizontal and vertical with
the very high sensitivity on the central axis. Note: At 50% of on-axis
distance horizontally and indoors at very high sensitivity the FoV can extend to 120°
(+/-60°).
Note: See Appendix 2: FS24X Plus™ FM Performance Appendix for FM 3260 FoV
performance.
EN 54-10 Field of View approved to symmetrical 90° (45° off axis
horizontal and vertical rotation).
FSX Plus flame detectors are compatible with the Honeywell® TL-
1055 and TL-2055 FSX test lamps.
Verification test distance: 3 to 8m (10 – 25 ft) at high sensitivity.
Recommended test every 3 months.
24 VDC nominal (18-32 VDC) - Regulated
1.8 Watts (nominal)
2.4 Watts (Alarm)
12 Watts (max) = 0.50 A @ 24 V with heater ON 100% duty cycle.
-55°C to +75°C
-55°C to +85°C
-50°C to +75°C
-50°C to +85°C
11

Advertisement

Table of Contents
loading

Table of Contents