Safety

For additional Cautions and Warnings, see Appendices
Installation, Commissioning, Periodic Testing, Calibration, and all other Maintenance must be
l
performed only by trained professionals.
Install in accordance with all local codes.
l
Follow all warnings, cautions, and instructions.
l
The suitability of the system installed is the responsibility of that system's designer and
l
installer.
Routinely check the system for proper operation and/or damage.
l
Replace damaged and/or non-operating devices.
l
Install only in areas in accordance with the environmental and hazardous area ratings.
l
Carefully review mounting area and position in accordance with the FS24X Plus™ FM
l
Performance Appendix and this Manual to ensure optimal flame detection regarding the
angle of device and unobstructed view.
Avoid potential sources of direct or indirect radiation in the flame detector field of view.
l
Do not touch the sensors on the front of the electronics module.
l
Avoid direct sunlight into the flame detector window – use provided sunshade, aim flame
l
detectors down at 40 degrees or more when possible, and use multiple detectors to cover
hazardous areas from different directions.
Avoid close proximity to rapid modulation/chopping of sunlight (creating moving dark
l
shadows) as optical sensor performance can be reduced, e.g. close trees in the wind, rotating
blades.
Honeywell® FS24X Plus™ |

Introduction

RISK OF IMPROPER FLAME DETECTION
RISK OF IMPROPER FLAME DETECTION