Combined Alarm and Fault Relay Interface Circuits
Fault relay configured normally energized and wired using ordinarily open contact. i.e.,
l
continuity of signal circuit will be broken if relay de-energized.
Any loss of continuity in the power circuit will result in fault relay being de-energized and
l
fault condition being signaled to the controller.
Alarm relay usually configured de-energized and wired using the normally open circuit. i.e.,
l
the signal circuit is shorted in the event of an alarm.
The EOL resistor (selected following control panel specification) enables the signal circuit to
l
be monitored by the control panel for continuity.
Any loss of continuity in the signal circuit, including the disconnect of either the signal
l
conductor, or the EOL resistor, or both will be detected by the controller and signal as a fault.
The termination of the alarm circuit conductor and the EOL resistor (or the next unit in a
l
daisy chain of units) must be inserted into separate openings on the duplicate terminal block
of the NFPA 72 Connection Kit to comply with NFPA 72 requirements.