Rigid Wall Installation Mf2 Installation Frame (Circular) - Swegon Actionair ThermShield FD Installation Manual

Mf on wall / floor installation method
Hide thumbs Also See for Actionair ThermShield FD:
Table of Contents

Advertisement

ThermShield MF On Wall Installation Method
Rigid wall installation
MF2 installation
frame
Damper blade must be closed during installation!
The wall is composed of concrete blocks (minimum
density of 550 kg/m³) or reinforced concrete (minimum
density of 2200 kg/m³) and with a minimum thickness
of 100 mm.
1. Create an opening in the wall (FDC25- Ød +10
mm, FDC40-Ød + 25 mm).
2. Place the damper in the opening.
3. Fasten the fire damper with screws
FDC25- 4 pieces, 6(d)x160(l) mm,
FDC40- 12 pieces, 6(d)x160(l) mm.
Ensure that the damper is sufficiently supported.
Test the operation of the damper blade.
10
Swegon reserves the right to alter specifications.
1
20210615 - L00010
2
3