Vertical Damper Installation In A Plasterboard Wall With Pattress - Swegon actionair DWFX-C Installation Manual

Table of Contents

Advertisement

VERTICAL BLADES;
Damper can be installed with the blades in the
vertical orientation with the actuator mounted at
either the top or bottom refer to drawings for cleat
locations;
DWFX-C actuator at top = AA-SS-2000
DWFX-C actuator at bottom = AA-SS-2001

Vertical Damper Installation in a
Plasterboard Wall with Pattress
Actionair SmokeShield PTC - [AA/F 10708] (Illustrated
above)
Actionair FireShield - [AA/F 10709]
Installation Method
1. Fit track (of partition) to the ceiling.
2. Suspend the damper from the ceiling through the
centre of the partition ceiling track using 10mm stud-
ding drop rods.
3. Frame out the damper using tracks and studs lined
with board. This is done with a lined track above the
damper crossing between the nearest two full height
studs, two vertical lined studs as close to the damper
as possible (outside the cleats) from the top cross track
to the floor and a lined cross track below the damper
between the two vertical studs.
4. Build the partition to the track and stud framework,
between 50 mm - 60 mm to the damper.
5. Insulate the wall with mineral/stone wool (if required).
6. Seal the damper to the partition with intumescent
sealant and add pattresses to both sides down to the
damper spigot, seal to the damper spigot with intu-
Actionair DWFX-C Installation Guide















7. Finish the wall as standard practice.
8. A minimum of 200 mm between fire dampers installed
20220503 - LNNN00353 (5.0) Swegon reserves the right to alter specifications.














mescent sealant.
in separate ducts and 75 mm between fire damper and
a construction element (wall/floor).
³


















³




© Swegon Air Manage
South Street, Whitstable
Tel: +44 (0)1227
Email: actionair@sw
www.swegon.c
Installation
If your proposed installation
that shown here, please dis
authority having jurisdiction
documentation.
Deviation from this drawing
of the relevant authority.
Connecting ductwork omitte
Ductwork must be indepen
There must be an appropria
joint between the damper a
ductwork on both sides of t
A minimum of 200mm betw
installed in separate ducts
fire damper and constructio
needs to be observed unles
specified in the drawing.
SC
Plea
for la
co
Inst
and
G
ECN2227
F
ECN1999
E
EC1830
D
EC1770
Rev:
Comments:
swehrle
Drawn By:
Kimberley.M
Checked By:
Gore.S
Approved By:
Description:
VERTICAL APPL
SMOKE SHIELD
PLASTERBOAR
Damper Size Ra
200 x 200 to 100
Reference No:
AAF10708
1
3

Advertisement

Table of Contents
loading

Table of Contents