Installation; Wiring - Emerson Facility E2 Installation And Operation Manual

Status display
Hide thumbs Also See for Facility E2:
Table of Contents

Advertisement

2

Installation

This section of the manual covers wiring and mounting for the FSD.

2.1. Wiring

1. Step 1: Using the four screws on the front
of the mounting plate, unscrew the cover
of the FSD and remove, exposing the
back of the enclosure. Once the top has
been separated from the back of the en-
closure, unplug the 8-pin connector and
RS232 cable (Step 1 of Figure 2-1) from
the circuit board (P/N 537-1100).
2. Step 2: Mount the base enclosure and re-
fer to Section 2.3., Mounting for instruc-
tions.
3. Step 3: Once the unit has been mounted,
depending on the voltage input, wire ei-
ther 120VAC, 208VAC, or 240VAC Hot
leg to the corresponding terminal block
label. Then wire the Neutral or L2 leg to
the terminal block labeled Neutral. Wire
Ground to Ground as indicated by Step 3
of Figure 2-1.
NOTE: Provide either 120VAC, 208VAC,
or 240VAC (40VA max) to the FSD termi-
nal block through a store circuit breaker.
The breaker size should be 20 amps or less.
2 • FSD Installation and Operation Guide
STEP 3
Hot in
Transformer
Inside Back of Enclosure
Figure 2-1 - 8-Pin Connector and RS232 Cable Connections
4. Step 4: Open the ferrite (P/N 090-0008)
and run the Ethernet cable through, wrap-
ping the cable around the ferrite twice
(two turns), near the Ethernet port (LAN)
on the back of the display, and close the
ferrite (Figure 2-2) around the Ethernet
cable.
Figure 2-2 - Ferrite Installation on Ethernet Cable
5. Step 5: Plug the Ethernet cable into the
RJ45 connector (LAN) on the back of the
9.0"
STEP 1
_
+ _
_
AUX
+
+
FSD Circuit
Board
026-1400 Rev 2 12-APR-10
8.0"

Advertisement

Table of Contents
loading

Table of Contents