Snooze Delay
Snooze Delay sets the number of minutes to silence
the audible alarm buzzer when the snooze button on
the FSD is touched.
Min Alarm Priority
This alarm priority setting specifies a minimum prior-
ity for alarms to be filtered. Alarms with a priority
greater than the Minimum Alarm Priority will not be
shown. Alarms with a priority equal to or lower than
this value will be shown.
(1 to 99 range: 1=highest, 99=lowest)

5.4.2. Communications Tab

Figure 5-12 - Communications Screen - Set E2 Parameters
E2 IP Address
Enter the IP address or Hostname of the E2 from
which the FSD will be receiving alarms. Note that if
more than one E2 controller is at a site, one E2 must
be set up as the alarm annunciator for that site. (See
Section 6, E2 Data Point Setup for FSD.) The FSD
will receive alarms from that alarm-annunciator E2
for the entire site. The FSD will point only to a single
E2 at a site (it will not poll multiple controllers for
alarms).
For multiple E2s at a site, enter the IP address of the
alarm-annunciator E2. If one E2 is located at a site,
enter the IP address for that single E2.
E2 IP Port
The E2 IP Port is the port number used by the FSD to
connect with the E2 unit. The port number in this field
must match the FSD Client Port field in the E2 for
the FSD and the E2 to communicate. The default port
is 14106.
12 • FSD Installation and Operation Guide
Press Alt + T on the E2 to locate the FSD Client Port
field. If a different port is desired, enter that port num-
ber in this field.
Display Number
The display number is the FSD device number in the
E2. This number is the FSD's unique address and the
application to which it corresponds.

5.4.3. General Tab

Under General configuration the FSD name is shown
with Reboot Unit and Exit Application options.
Touch Reboot Unit to restart the FSD. Exit Applica-
tion will exit this General configuration screen and go
to the Boot Loader or Start up screen.
Figure 5-13 - General FSD Information Screen

5.4.4. About Tab

Read-only, general information about the FSD is dis-
played on this screen including copyright and revision
information. Touch OK or Cancel to exit the About
screen and return to the Home screen.