Electrical
Nominal operating voltage: 230V AC rms ± 10%
Operating frequency: 50Hz
Power consumption: <2.5W
Power: from mains socket under test
Non-trip earth loop impedance ranges:
Earth loop threshold accuracy: ± (10% + 0.3Ω) Note 1
Voltage low indication: <195V ± 5%
Voltage high indication: >270V ± 5%
Earth neutral voltage high indication: > 30V nominal
Open earth indication: >500Ω ± 10%
RCD test current at 195V: 30mA (EZ365 only)
Duration of RCD test current: 300ms (EZ365 only)
Polarity reversal test (EZ365 only)
Specification
EZ165 / EZ365
0 - 1.7 - 5 - 10 - 100 - 200 - 500Ω