3.3.1 Wiring and Voltage Check
The condition of the wiring at the socket under test or any out of
tolerance supply voltage will be indicated by the LED sequences
of figure 1 on the lower row of LED's. If a wiring fault is detected
or the supply voltage is out of tolerance the top loop indicator
LED's will not illuminate as a loop impedance measurement is
not made.
Figure 1. Wiring and Voltage Test Indicators (Lower LED's)
In the event of a fault being indicated, investigation should only
be carried out by a suitably qualified electrician.
7
Wiring Correct, Voltage OK
Wiring Correct, Voltage high >270V
Wiring Correct, Voltage low <195V
Earth-Neutral voltage >30V
Open Neutral
Open Earth >500Ω
Phase (Live) Fault
Phase-Neutral Reversal
Phase-Earth Reversal
Serious wiring fault or voltage <135V