Pulsed tone increasing to
continuous tone
3.3 Using the EZ165 & EZ365
Plug the EZ165 or EZ365 into the socket to be tested.
The wiring test is performed first. As the test is performed, the
lower LED's flash orange in sequence, until the test is complete
and the result is then displayed. Compare the status of the flashing
indicators with the front decal or with figures 1, 2 & 3 in sections
3.3.1 and 3.3.2.
If the wiring test is successful, then the loop impedance test is
performed. The top row of LED's will flash orange in sequence
until the test is complete. When the test is complete, the result
is displayed. If the wiring test detected a fault, then the loop
impedance test is not performed.
If the EZ165 / EZ365 does not power up and none of the
LED's illuminate this could mean that the wiring is incorrect,
or the mains voltage is less than 135V and investigation of the
wiring is required. In such circumstances verify the EZ165 /
EZ365 in a known correctly wired socket to confirm the need
for investigation.
RCD trip test will be activated in 2
seconds